B.2 Parameter Table
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07) 389
Parameter List
B
L5-02
Auto Restart
Operation Selection
Sets fault contact activation during automatic
restart attempts.
0: No Fault Relay - fault contact will not
activate during an automatic restart attempt.
1: Fault Relay Active - fault contact will
activate during an automatic restart attempt.
0,1 0 A A A 49F
L5-04
Fault Reset Interval
Time
Sets the amount of time to wait between
performing fault restarts. Enabled when L5-05
is set to 1.
0.5 to
600.0 s
10.0
s
AAA 46C
L5-05
Fault Reset Operation
Selection
Internally logs the quantity of restart attempts
after a fault.
0: Use the method available in G7.
1: Use the method available in V7.
0 to 1 0 A A A 467
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/
f
O
L
V
P
M

Table of Contents

Other manuals for YASKAWA V1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 Series and is the answer not in the manual?

YASKAWA V1000 Series Specifications

General IconGeneral
ModelV1000 Series
SeriesV1000
Output Frequency0.1 to 400 Hz
Overload Capacity150% for 60 seconds
TypeAC Drive
Control MethodV/f Control
Input Voltage200-240V, 380-480V
Output Voltage0 to Input Voltage
Power Range0.1 to 18.5 kW
Horsepower0.2 to 25 HP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication InterfacesModbus RTU
EnclosureIP20
Ambient Temperature-10 to +50°C
Storage Temperature-20 to +60°C
Humidity5 to 95% RH (non-condensing)
Cooling MethodFan Cooled