B.2 Parameter Table
392 YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
L6-08
Mechanical
Weakening Detection
Operation
0: Mechanical Weakening Detection disabled.
1: Continue running if the speed (signed) is
greater than L6-09 (alarm only).
2: Continue running if the speed (not signed) is
greater than L6-09 (alarm only).
3: Interrupt drive output when the motor speed
(signed) is greater than L6-09 (protection
operation).
4: Interrupt drive output when the motor speed
(not signed) is greater than L6-09 (protection
operation).
5: Continue running if the speed (signed) is
less than L6-09 (alarm only).
6: Continue running if the speed (not signed) is
less than L6-09 (alarm only).
7: Interrupt drive output when the motor speed
(signed) is less than L6-09 (protection
operation).
8: Interrupt drive output when the motor speed
(not signed) is less than L6-09 (protection
operation).
0 to 8 0 A A A 468
L6-09
Mechanical
Weakening Detection
Speed Level
Sets the speed that triggers mechanical
weakening detection.
Uses torque detection 1 to set the torque (L6-
01 to L6-03).
When L6-08 is set for an unsigned value, the
absolute value is used even if the speed is a
negative value.
-110.0
to
+110.0
%
110
%
AAA 469
L6-10
Mechanical
Weakening Detection
Time
Sets the time required for a mechanical
weakening condition to exist before triggering
parameter L6-08.
0.0 to
10.0 s
0.1 s A A A 46A
L6-11
Mechanical
Weakening Detection
Start Time
Mechanical weakening detection is triggered
when the cumulative operation time (U4-01)
exceeds this value. When one of the multi-
function outputs is set for mechanical
weakening detection (H2-= 22) the output
signal is switched on.
0 to
65535
0AAA46B
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/
f
O
L
V
P
M

Table of Contents

Other manuals for YASKAWA V1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 Series and is the answer not in the manual?

YASKAWA V1000 Series Specifications

General IconGeneral
ModelV1000 Series
SeriesV1000
Output Frequency0.1 to 400 Hz
Overload Capacity150% for 60 seconds
TypeAC Drive
Control MethodV/f Control
Input Voltage200-240V, 380-480V
Output Voltage0 to Input Voltage
Power Range0.1 to 18.5 kW
Horsepower0.2 to 25 HP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication InterfacesModbus RTU
EnclosureIP20
Ambient Temperature-10 to +50°C
Storage Temperature-20 to +60°C
Humidity5 to 95% RH (non-condensing)
Cooling MethodFan Cooled