B.2 Parameter Table
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07) 399
Parameter List
B
n8: Permanent Magnet (PM) Motor Control
Use n8 parameters to control the PM motor control.
n8-45
<30>
Speed Feedback
Detection Control
Gain
Sets the gain for internal speed feedback
detection control. This parameter does not
typically require adjustment.
Increase this setting if hunting occurs.
Decrease to lower the response.
0.0 to
10.0
1.0 −−A538
n8-47
<30>
Pull-In Current
Compensation Time
Constant
Sets the time constant to make the pull-in
current and actual current value agree.
Decrease the value if the motor begins to
oscillate.
Increase the value if it takes too long for the
current reference to equal the output current.
0.0 to
100.0 s
5.0 s −−A 53A
n8-48
<30>
Pull-In Current
Defines the amount of current provided to the
motor during no load operation at a constant
speed.
Set as a percentage of the motor rated current.
Increase this setting when hunting occurs while
running at a constant speed.
0 to
200%
0% −−A 53B
n8-49
<30>
Load Current
Sets the amount of d-axis current when using
Energy Saving control.
-200 to
0%
0% −−A 53C
n8-50
Heavy Load Current
Level (for PM)
Sets the load level to begin high-efficiency
control of an PM motor.
50 to
255%
80% −−A 53D
n8-51
<30>
Acceleration Time
Pull-In Current
Sets the pull-in current during acceleration as a
percentage of the motor rated current (E5-03).
Set to a high value when more starting torque
is needed.
0 to
200%
50% −−A 53E
n8-55
<30>
Load Inertia
This value should be set to correspond to load
inertia.
0: The inertia ratio between the motor and the
load just less than 1:10.
1: The inertia ratio between the motor and the
load is 1:10 to 1:30.
2: The inertia ratio between the motor and the
load is 1:30 to 1:50.
3: The inertia ratio between the motor and the
load is greater than 1:50.
0 to 3 0 −−A 56E
n8-56
High Performance
Control Selection
0: Disabled
1: Enabled
0,1 1 −−A 56F
<12> Default setting value is dependent on parameter o2-04, Drive/kVA Selection.
<30> For use with PM motor.
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/
f
O
L
V
P
M