602 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 10 EtherNet/IP Communication
7. To access the data provided by the E300 relay EtherNet/IP
Communication Module, navigate to input tags created by the Generic
Profile. Ta b le
565 represents the Input Assembly data.
Table 565 - Instance 199 - Input (Produced) Assembly
Bit
INT DINT1514131211109876543210
0
0 Reserved for Logix
1
2
1
DeviceStaus0
3
DeviceStaus1
4
2
InputStatus0
5
InputStatus1
6
3
OutputStatus
7
OpStationStatus
8
4
TripSt sCur rent
9
WarnStsCurrent
10
5
Tri pStsVolta ge
11
WarnStsVoltage
12
6
Tri pStsPowe r
13
WarnStsPower
14
7
TripSt sControl
15
WarnStsControl
16
8
TripSt sA na log
17
WarnStsAnalog
18
9Reserved
19
20
10
ThermUtilizedPct
CurrentImbalance
21
AvgPercentFLA
22
11 AverageCurrent
23
24
12 L1Current
25
26
13 L2Current
27
28
14 L3Current
29
30
15
GFCurrent
31
Reserved
32
16
AvgVoltageLtoL
33
L1toL2Voltage
34
17
L2toL3Voltage
35
L3toL1Voltage

Table of Contents

Other manuals for Allen-Bradley E300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley E300 and is the answer not in the manual?

Allen-Bradley E300 Specifications

General IconGeneral
TypeElectronic Overload Relay
MountingDIN Rail or Panel Mount
Protection ClassIP20
Voltage Range24…690 V AC/DC
Communication OptionsEtherNet/IP, DeviceNet
ProtectionOverload, phase loss, ground fault
Operating Temperature-20°C to 60°C