● Gate sensor activation delay set within 0.5-2.0 seconds. This parameter is used to
ignore short-term when detecting passing vehicles with a trailer or other
parts that are transparent to the sensor.
● Other parameter values are not fundamental and may be left at their default values.
● After setting up, click OK. All the parameter values will be applied automatically.
10.21 Connecting SEA drives with MPU/0 control unit
To connect to MPU/0 control unit, you need to switch the controller to the third-party gate
controller handling mode according to the logic defined in the Control Program.
Table 123. Settings of CONF1 dip-unit toggles for operating with the MPU/0
The toggle selects the normal state of the control STOP button. ON normally closed,
OFF normally open. For the wiring diagram of the control panel, refer to Sec. 10.5 Connecting the
gate control panel.
The toggle selects the configuration of vehicle presence sensors. ON only one (the central) is
connected, OFF all three are connected (at the entrance, in the center and at the exit). For the
wiring diagram of vehicle presence sensors, refer to Sec. 10.6 Connecting vehicle presence sensors.
Pic 127. Connecting MPU/0 control unit
The rest of the unit terminals (mains, electric motor, indicator lights) are connected according to
the original instruction for MPU/0 control unit.
Table 124. Setting the micro toggle switch on the MPU/0 control unit board