Modbus Read, Write and Override Parameters plus Exception Codes
432 UDC3500 Universal Digital Controller Product Manual 3/07
10.7.24 Display
Table 10-33 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Display.
Table 10-33 Set-up Group – Display
Parameter
Register
Address
Data
Type
Access Data Range or
Enumerated Selection
Description ID Hex Decimal
Decimal Point
Location
155 009B 155 INT R/W
0 = None – Fixed
1 = One – Floating
decimal point to one
2 = Two – Floating
decimal point to two
3 = Three – Floating
decimal point to three
Decimal Point
Location Loop2
155 019B 411 INT R/W
0 = None – Fixed
1 = One – Floating
decimal point to one
2 = Two – Floating
decimal point to two
3 = Three – Floating
decimal point to three
Temperature
Units
129 0081 129 INT R/W
0 = °F
1 = °C
2 = None
Power Frequency 166 00A6 166 INT R/W 0 = 60 Hertz
1 = 50 Hertz
Ratio Input 2
from Front Panel
208 00D0 208 INT R/W 0 = Disable
1 = Enable
Language
(Displays)
192 00C0 192 INT R/W 0 = English
1 = French
2 = German
3 = Spanish
4 = Italian
TC Diagnostics 159 009F 159 INT R/W 0 = Enable
1 = Disable
Unit ID Number* 41 0029 41 INT R/W 0 to 255
* The Unit ID Number parameter can be used to uniquely identify a particular
instrument.