EasyManuals Logo

Honeywell UDC3500 User Manual

Honeywell UDC3500
460 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #448 background imageLoading...
Page #448 background image
Modbus Read, Write and Override Parameters plus Exception Codes
432 UDC3500 Universal Digital Controller Product Manual 3/07
10.7.24 Display
Table 10-33 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Display.
Table 10-33 Set-up Group – Display
Parameter
Register
Address
Data
Type
Access Data Range or
Enumerated Selection
Description ID Hex Decimal
Decimal Point
Location
155 009B 155 INT R/W
0 = None – Fixed
1 = One – Floating
decimal point to one
2 = Two – Floating
decimal point to two
3 = Three – Floating
decimal point to three
Decimal Point
Location Loop2
155 019B 411 INT R/W
0 = None – Fixed
1 = One – Floating
decimal point to one
2 = Two – Floating
decimal point to two
3 = Three – Floating
decimal point to three
Temperature
Units
129 0081 129 INT R/W
0 = °F
1 = °C
2 = None
Power Frequency 166 00A6 166 INT R/W 0 = 60 Hertz
1 = 50 Hertz
Ratio Input 2
from Front Panel
208 00D0 208 INT R/W 0 = Disable
1 = Enable
Language
(Displays)
192 00C0 192 INT R/W 0 = English
1 = French
2 = German
3 = Spanish
4 = Italian
TC Diagnostics 159 009F 159 INT R/W 0 = Enable
1 = Disable
Unit ID Number* 41 0029 41 INT R/W 0 to 255
* The Unit ID Number parameter can be used to uniquely identify a particular
instrument.

Table of Contents

Other manuals for Honeywell UDC3500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell UDC3500 and is the answer not in the manual?

Honeywell UDC3500 Specifications

General IconGeneral
BrandHoneywell
ModelUDC3500
CategoryController
LanguageEnglish

Related product manuals