EasyManua.ls Logo

Honeywell UDC3500 - Read Software Options Status; Table 10-2 Option Status; Figure 10-1 Software Option Status Information

Honeywell UDC3500
460 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Modbus Read, Write and Override Parameters plus Exception Codes
3/07 UDC3500 Universal Digital Controller Product Manual 351
10.3 Read Software Options Status
Read
Doing a Read of register address 00B9 listed in Table 10-2 will tell you which of the
available options are enabled / installed or disabled / not installed.
Table 10-2 Option Status
Parameter Register
Address
Data Type Access Data Range or
Enumerated Selection
Description ID Hex Decimal
Option Status
(Read only)
185 00B9 185 INT RD See Figure 10-1.
The data field in the response message will be a decimal number from 0 to 255. Convert
the decimal number to binary as shown in Figure 10-1
.to determine which options are or
are not active.
00001111
0 to 255
Convert decimal to binary
0 = not installed
1 = installed
Loop 2
Setpoint Programming
Math
Health Watch
EXAMPLE: 15
Binary
Loop 2 – installed
SP Programming – installed
Math – installed
Health Watch - Installed
0000111100001111
0 to 255
Convert decimal to binary
0 = not installed
1 = installed
Loop 2
Setpoint Programming
Math
Health Watch
EXAMPLE: 15
Binary
Loop 2 – installed
SP Programming – installed
Math – installed
Health Watch - Installed
Figure 10-1 Software Option Status Information

Table of Contents

Other manuals for Honeywell UDC3500

Related product manuals