EasyManuals Logo

Honeywell UDC3500 User Manual

Honeywell UDC3500
460 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #301 background imageLoading...
Page #301 background image
Input Calibration
3/07 UDC3500 Universal Digital Controller Product Manual 285
5.4.4 Radiamatic, Millivolts, Volts, Carbon, Oxygen or Thermocouple Differential
Inputs
Refer to Figure 5-5 and wire the controller according to the procedure given in Table 5-6.
Table 5-6 Set Up Wiring Procedure for Radiamatic, Millivolts, Volts,
Carbon, Oxygen or Thermocouple Differential Inputs (Except 0-10 Volts and
–1 to 1 Volts)
Step Action
1
Connect the copper leads from the calibrator to the Input #1 terminals as shown in
Figure 5-5.
2
Place voltage source at zero before switching on.
3
Following calibration, turn off the voltage source prior to disconnecting it from the
instrument.
ATTENTION
For Radiamatic inputs only, set Emissivity value to 1.0.
See:
Subsection 3.15 – Configuration Set Up prompt INPUT 1, function prompt EMISSIV 1
Subsection 3.16 – Configuration Set Up prompt INPUT 2, function prompt EMISSIV 2
Subsection 3.17 – Configuration Set Up prompt INPUT 3, function prompt EMISSIV 3
Millivolt or
Volt Source
+
_
30-
29+
31R
32+
33-
34R
35+
36-
28R
Input 1
Input 2
Input 3
Figure 5-5 Wiring Connections for Radiamatic, Millivolts, Volts, Carbon,
Oxygen or Thermocouple Differential Inputs (Except 0-10 Volts and –1 to 1
Volts)

Table of Contents

Other manuals for Honeywell UDC3500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell UDC3500 and is the answer not in the manual?

Honeywell UDC3500 Specifications

General IconGeneral
BrandHoneywell
ModelUDC3500
CategoryController
LanguageEnglish

Related product manuals