Monitoring and Operating the Controller 
3/07  UDC3500 Universal Digital Controller Product Manual  213 
Error Code 
(Upper Display) 
 
Definition 
 
Fix 
the ACCUTUNE process. 
LOW PV 
LOW PV 
Applies only to SP or SP+PV 
tuning. PV did not change 
sufficiently or the PV has 
increased by more than 4% 
but Deadtime was not 
determined. 
No action necessary. After approximately five 
minutes, the instrument will automatically attempt 
another SP adaptive tuning process using a larger 
output step. 
 
Aborting Accutune 
To abort Accutune and return to the last previous operation (SP or output level), press 
MAN-AUTO key to abort the Accutune process or increment from the “DO SLOW” or 
“DO FAST” prompt to the “TUNE OFF” prompt. 
Completing Accutune 
When Accutune is complete, the calculated tuning parameters are stored in their proper 
memory location and can be viewed in the TUNING Set up Group, and the controller 
will control at the local setpoint using these newly calculated tuning constants. 
4.11   Fuzzy Overshoot Suppression 
Introduction 
Fuzzy Overshoot Suppression minimizes Process Variable overshoot following a setpoint 
change or a process disturbance. This is especially useful in processes that experience 
load changes or where even a small overshoot beyond the setpoint may result in damage 
or lost product. 
How it works 
The Fuzzy Logic in the controller observes the speed and direction of the PV signal as it 
approaches the setpoint and temporarily modifies the internal controller response action 
as necessary to avoid an overshoot. There is no change to the PID algorithm, and the 
fuzzy logic does not alter the PID tuning parameters. This feature can be independently 
Enabled or Disabled as required by the application to work with the Accutune algorithm. 
Fuzzy Tune should not be enabled for processes that have an appreciable amount of 
deadtime. 
Configuration 
To configure this item, refer to Section 3 – Configuration: