Configuration 
3/07  UDC3500 Universal Digital Controller Product Manual  93 
3.12 Math Set Up Group 
Introduction 
These selections are provided only as part of the Math Options package. 
 
ATTENTION 
Enabling SP Program 4 automatically disables the characterizers in the Math 
Setup Group. 
Function Prompts 
Table 3-12 MATH Group Function Prompts 
Function Prompt  
Lower Display 
Selections or  
Range of Setting  
Upper Display 
Parameter  
Definition 
8SEG CH1 
 
 
 
DISABLE 
INPUT1 
INPUT2  
INPUT3  
INPUT4  
INPUT5 
L1 OUT 
 
 
 
L2 OUT  
 
8 SEGMENT CHARACTERIZER #1—An eight-
segment characterizer can be applied to any analog 
input, Output 1 or Output 2. 
DISABLE—Disables characterizer. 
INPUT 1—Characterizer is applied to Input 1. 
INPUT 2—Characterizer is applied to Input 2.  
INPUT 3—Characterizer is applied to Input 3.  
INPUT 4—Characterizer is applied to Input 4.  
INPUT 5—Characterizer is applied to Input 5. 
LOOP 1 OUTPUT—Characterizer is applied to Loop 
1 Output. – Should not be used for Three Position 
Step Control or Position Proportional Control 
applications 
LOOP 2 OUTPUT—Characterizer is applied to Loop 
2 Output. 
There are eight (Xn) Input values and eight (Yn) 
Output values to be selected. The following rules 
apply: 
•  When any analog input is used, the Input Ratio 
and Bias for that input are applied to the Xn 
Values. 
•  When one of the Loop outputs are selected, the 
Xn Input values are the Output from the control 
algorithm, and the Yn Output is the final control 
element action. This application is useful for non-
linear control elements or Process Variable. 
 
A simple example is shown in 
Figure 3-2.