Configuration 
3/07  UDC3500 Universal Digital Controller Product Manual  91 
 
Figure 3-1  Mass Flow Example 
 
Example  - Mass Flow Compensation
 
 gas flow rate of 650 SCFM develops a differential pressure of 90" H  O across an orifice plate  
at reference conditions of 30 psig and 140  F. Compensate this gas flow for temperature and  
pressure variations. 
pply Multiplier/Divider Algorithm: 
Flow = K 
DP 
f 
x  P 
f 
T 
f
 
T 
ref
x 
P 
ref
PV  = K 
(Input B x Ratio B + Bias B) 
(Input A x Ratio A + Bias A) x (Input C x Ratio C + Bias C) 
X  (Calc     – Calc     ) 
HI
 
LO
Where: 
         
     f = flowing conditions          
     ref = reference conditions (in absolute units) 
Note: If temperature and pressure signals are already ranged in absolute units,  
no Bias is required for inputs B and C. 
ssign inputs using Engineering units: 
Let: 
  
  Input A = DP  = IN1 (in H  O)  
  Input B = T = IN2 + Bias2 = IN2  F + 460 ( R)  
  Input C = P = IN3 + Bias3 = IN3psig + 14.7(psia)  
  T          = 140  F + 460 = 600  R  
  P          = 30 psig + 14.7 = 44.7 psia  
  Calc     = 650.0  
  Calc     = 0.0        
2
f
 
f 
ref
 
ref 
Hi
 
Lo 
Flow in SFCM at Reference Conditions 
K = to be determined next 
f 
2
22049
Example continued 
on next page
PV = Q     = 
DP 
f
 
(IN3 + 14.7) 
x 
SCFM 
(IN2 + 460) 
K
2
x
(650.0 - 0.0) 
x
DP 
f 
90 
(IN3 + 14.7) 
x 
(IN2 + 460) 
T 
ref
x
P
ref
SCFM
 
Q          = 
x
650 
Note: When IN2 and IN3 are at the reference conditions of 600  R (140  F) and 44.7psia (30  
psig) respectively and DP  = 90" H  O, the equation must calculate 650 SCFM. To accomplish  
this, divide the DP value by "90" to normalize the equation. 
2
f 
Rearranging terms: 
Variable 
Constant = K 
2
DP 
f 
(IN3 + 14.7) 
x 
(IN2 + 460) 
x
1 
90 
T 
ref
P
ref
x x
650 
SCFM 
Q          =