Configuration 
90  UDC3500 Universal Digital Controller Product Manual  3/07 
Function Prompt  
Lower Display 
Selections or  
Range of Setting  
Upper Display 
Parameter  
Definition 
Math Algorithm Notes: 
1.  Calculation ranges for the Math Algorithms are set via CALC HI and CALC LO parameters and 
are between –999. and 9999. The SP High and Low values (SP Range) are independent of 
these settings and can be any value between –999. and 9999. 
2.  The CALC HI and CALC LO values determine the range limits for the SP High and Low values 
for the Weighted Average, Summer, Hi Select and Low Select algorithms.  
3.  Does not apply to Three Position Step Control. 
4.  If the calculated value of the quantity under the square root sign decreases to a value less than 
0.010, then the calculation will become linear as the calculated value decreases below 0.010. 
5.  Input 2 is always used in all of the Feedforward algorithms. 
6.  When Relative Humidity is selected as the Input Algorithm, both Input 1 (Wet Bulb) and Input 2 
(Dry Bulb) are forced to the RTD 100 Ohm Low activation. This activation normally has a range 
of a -300 to 300ºF (-184 to 149ºC). However, for Relative Humidity, the range of both inputs is 
restricted such that the Input measurements below 21ºF or above 212ºF (-6 ºC or 100ºC) for 
either input will result in an Input Range diagnostic message being shown on the lower display. 
This is because input values outside of this range will not calculate valid %RH values. If the 
calculated %RH value falls below zero, the “RH LOW” diagnostic message will appear on the 
lower display.