Monitoring and Operating the Controller 
214  UDC3500 Universal Digital Controller Product Manual  3/07 
Set Up Group “ACCUTUNE” 
Function Prompt “FUZZY” 
Select “ENABLE” or “DISABLE” – Use  or . 
 
4.12   Using Two Sets of Tuning Constants 
Introduction 
You can use two sets of tuning constants for single output types and choose the way they 
are to be switched. (this does not apply for Duplex control, which always uses two PID 
sets). 
The sets can be: 
•  keyboard selected, 
•  automatically switched when a predetermined process variable value is reached,  
•  automatically switched when a predetermined setpoint value is reached.  
Set up Procedure 
The following procedure  (Table 4-16) to: 
•  select two sets, 
•  set the switch-over value,  
•  set tuning constant value for each set. 
Table 4-16  Set Up Procedure 
Step  Operation  Press  Result 
1 
Select Control  
Set-up Group 
Setup 
Until you see: 
Upper Display = SET  
Lower Display = CONTROL 
2 
Select PID SETS 
Func 
Until you see: 
Upper Display = (available selections) 
Lower Display = PID SETS 
3 
Select PID SETS 
Function 
or  
To select the type of function. Available selections are: 
1 ONLY—1 set of constants 
2KEYBD—2 sets, keyboard selectable 
2PV SW—2 sets, auto switch at PV value 
2SP SW—2 sets, auto switch at SP value