Modbus Read, Write and Override Parameters plus Exception Codes 
3/07  UDC3500 Universal Digital Controller Product Manual  421 
10.7.20 Communications 
Table 10-29 lists all the register addresses and ranges or selections for the function 
parameters in Set-up Group Communications.  
Table 10-29  Set-up Group – Communications 
Parameter 
 
Register 
Address 
Data 
Type 
Access  Data Range or 
Enumerated Selection 
Description  ID  Hex  Decimal       
Shed Time  79  004F  79  INT  R/W  0 = No Shed 
1 = 255 sample periods 
Shed Mode and 
Output 
162 00A2  162  INT  R/W  0 = Last Mode and Last 
Output 
1 = Manual Mode, Last 
Output 
2 = Manual Mode, Failsafe 
Output 
3 = Automatic Mode 
Shed Setpoint 
Recall 
163 
 
00A3  163  INT  R/W  0 = To Last Local Setpoint 
used 
1 = CSP 
Computer Setpoint 
Ratio 
90 
 
005A 90  FP  R/W  –20.00 to 20.00 
Computer Setpoint 
Bias 
91 
 
005B 91  FP  R/W  –999 to 9999. 
Loop2 Computer 
Setpoint Ratio 
90 015A  346  FP  R/W  –20.00 to 20.00 
Loop2 Computer 
Setpoint Bias 
91 015B  347  FP  R/W  –999 to 9999. 
Communication 
Address 
77 
 
004D  77  FP  R/W  1 - 99 
Communications 
Type 
231 00E7  231  INT  R/W  0 = None 
1 = Disable 
2 = RS-485 Modbus 
3 = Ethernet only if installed 
IR Port Enable  241  00F1  241  INT  R/W  0 = Disable 
1 = Enable 
Baud Rate  232  00E8  232 INT R/W 0 = 4800 
1 = 9600 
2 = 19200 
3 = 38400 
Transmit Delay  78  004E  78  FP  R/W  Response Delay in ms 
(1 to 500) +6ms