Configuration 
3/07  UDC3500 Universal Digital Controller Product Manual  183 
WARNING 
After you change the IP Address, you will no longer be able to communicate with the instrument 
via Ethernet until you change the P.I.E. Tool’s IP Address setting in the “PC COMM SETUP” to 
match the setting that is now in your controller. 
 
Email Configuration Screen 
This controller may be configured to support up to two Emails. Each Email can be sent to 
a different address. Emails are sent only when the selected alarm transitions from the 
OFF to the ON state. 
 
Figure 3-4  Email Configuration Screen 
This controller cannot receive Emails, so it is suggested that you configure the “From 
Email:” window with a non-Email style address that will make it easy for you to 
determine which controller sent the Email. For Email technical reasons, the entry in the 
“From Email:” window cannot have spaces. See Figure 3-4. 
If you do not know your SMTP IP Address for outgoing Email, then contact your 
Information Technologies (IT) representative. If your PC is on the same LAN that will be 
used by the controller and which also connects to the Email server, then the SMTP IP 
Address may generally be found by opening a DOS shell and typing:  
ping smtp.[your domain name and extension, i.e., “yourisp.com”]