Modbus Read, Write and Override Parameters plus Exception Codes 
3/07  UDC3500 Universal Digital Controller Product Manual  411 
10.7.17 Control 
Table 10-26 lists all the register addresses and ranges or selections for the function 
prompts in Set-up Group Control. 
Table 10-26  Set-up Group – Control 
Parameter 
 
Register 
Address 
Data 
Type 
Access  Data Range or 
Enumerated Selection 
Description  ID  Hex  Decimal       
PV Source  133  0085  133  INT  R/W  0 = Input 1 
1 = Input 2 
2 = Input 3 
3 = Input 4 
4 = Input 5 
5 = Input AL1 
6 = Input AL2 
Tuning Parameter 
Selection 
172  00AC  172  INT  R/W  0 = One set only 
1 = 2 sets keyboard 
selected 
2 = 2 sets with PV 
automatic switchover 
3 = 2 sets with setpoint 
(SP) automatic switchover 
4 = Four sets Keyboard 
5 = Four sets PV switch 
6 = Four sets SP switch 
Automatic 
Switchover Value 
PID1 to PID2 (used 
with ID172 ) 
56  0038  056  FP  R/W  Within the PV Range in 
engineering units 
Automatic 
Switchover Value 
PID2 to PID3 (used 
with ID172 ) 
9  4009  16393  FP  R/W  Within the PV Range in 
engineering units 
Automatic 
Switchover Value 
PID3 to PID4 (used 
with ID 172 ) 
10  400A  16394  FP  R/W  Within the PV Range in 
engineering units 
Local Setpoint 
Source (Number of 
LSPs) 
173  00AD  173  INT  R/W  0 = One Local Setpoint 
1 = Two Local Setpoints 
2 = Three Local Setpoints 
3 = Four LSP