Monitoring and Operating the Controller 
3/07  UDC3500 Universal Digital Controller Product Manual  209 
4.10.3  Using AUTOMATIC TUNE at start-up for Duplex (Heat/Cool) 
Used when DUPLEX has been configured for AUTOMATIC. This is the preferred 
selection for most Heat/Cool applications when tuning a new chamber. This selection 
will sequentially perform both Heat and Cool tuning without further operator 
intervention. 
Table 4-10  Procedure for Using AUTOMATIC TUNE at Start-up for Duplex Control 
Step  Operation  Press  Result 
1 
Configure LSP1 
Lower 
Display
 
Until SP (Local Setpoint 1) shows 
in the lower display. 
2 
 
or  
Until LSP1 is a value within the 
Heat Zone (output above 50%). 
3 
Configure LSP2 
Lower 
Display
 
Until 2SP (Local Setpoint 2) shows 
in the lower display. 
4 
 
or  
Until LSP2 is a value within the 
Cool Zone (output below 50%). 
5 
Switch to 
“Automatic” Mode 
Man/Auto 
Until the “A” indicator is lighted (on 
controllers with Manual option). 
6 
Show Tuning 
Prompt 
Lower 
Display
 
Until “TUNE OFF” is shown on 
lower display. 
7 
Initiate Tuning 
 
Select “DO SLOW” or “DO FAST” 
in lower display. 
 
Tuning in operation 
Lower 
Display
 
Upper display will show a “T” as 
long as ACCUTUNE process is 
operating. When process 
completes, tuning parameters are 
calculated and lower display will 
show “NO TUNE” prompt.