FusionModule2000 Smart Modular Data Center
Installation Guide
10 Installing the Aisle Containment
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
104
To ensure a neat section after trimming, trim the PC plate using the aisle check tool in the No. 0 packing
box.
2. Use a marker to mark a line on the column where the PC plate closely attaches to the
column.
3. Move away the PC plate. Drill holes in the column and secure the L-shaped mounting
brackets to the column using plastic expansion bolts.
Figure 10-12 Securing L-shaped mounting brackets
(1) Column
Step 7 Install PC plates.
1. Pave the PC plate on the adjustable skylight.
2. Secure PC plate fasteners to PC plate supports.