FusionModule2000 Smart Modular Data Center 
Installation Guide 
 
Huawei Proprietary and Confidential                                     
Copyright © Huawei Technologies Co., Ltd. 
 
Figure 17-21 Connecting power cables to the circuit breaker 
 
 
6.  (Optional) If the intelligent battery monitoring system is not deployed, use a 04080376 
cable to connect the J1 port on the battery control board (BIB) to the corresponding port 
on the UPS. Alternatively, use a 04080377 cable for cascading and use a 04080376 cable 
for connecting to the corresponding port on the UPS. 
Figure 17-22 Connecting monitoring cables to the circuit breaker 
 
 
7.  (Optional) If an intelligent battery monitoring system is installed, see iBAT 
2.0-CIM01C2 User Manual for details about the installation, cable connection, and 
power-on of the BIM and CIM.