FusionModule2000 Smart Modular Data Center
Installation Guide
C Installation Verification
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
The gap between end doors is even.
â–¡ Compliant â–¡
Incompliant
After the end door is closed, the rubber strip in the
middle seals the gap properly.
â–¡ Compliant â–¡
Incompliant
After the double revolving door is closed, the height
deviation of the two door panels is less than 5 mm.
â–¡ Compliant â–¡
Incompliant
The rotating skylights work smoothly.
â–¡ Compliant â–¡
Incompliant
The end planes of skylight connective plates are flush
with each other.
â–¡ Compliant â–¡
Incompliant
The skylight electromagnet firmly suctions the skylight
when the power is on, and the skylight drops naturally
when the power is off.
â–¡ Compliant â–¡
Incompliant
All labels are correct, clear, and complete.
â–¡ Compliant â–¡
Incompliant
There is no foreign matter such as adhesive tape, cable
ties, paper, or packing materials left in and around the
aisle.
â–¡ Compliant â–¡
Incompliant
Cable Installation Checklist
All cable joints are secured properly, especially the cable
joints between network cables and cables inside cabinets.
â–¡ Compliant â–¡
Incompliant
Exposed parts near the wiring terminals and lugs are
wrapped with PVC insulation tape or heat shrinking
tubing.
â–¡ Compliant â–¡
Incompliant
All wiring terminals are securely installed with flat
washers and spring washers and are in good contact.
â–¡ Compliant â–¡
Incompliant
Cables are bound neatly, and cable ties are secured
evenly and properly in the same direction.
â–¡ Compliant â–¡
Incompliant
Cables are routed in a way convenient for maintenance
and capacity expansion.
â–¡ Compliant â–¡
Incompliant
All labels at the cable ends are clear.
â–¡ Compliant â–¡
Incompliant
Excess sections of cable ties are neatly cut.
â–¡ Compliant â–¡
Incompliant
There is no unnecessary adhesive tape or cable tie on