Electric Installation Checklist 
All ground cables are copper cables with diameters 
meeting the requirements. No switch or fuse is 
installed at the middle of a ground cable, and no 
short-circuit occurs. 
□ Compliant □ Incompliant 
Ground cables, AC input power cables, and 
internal cables are connected in accordance with 
the circuit diagram and screws are secured. No 
short-circuit occurs on power inputs or outputs. 
□ Compliant □ Incompliant 
Power cables and ground cables are not coiled and 
extra parts are cut off. 
□ Compliant □ Incompliant 
Lugs for power cables and protective ground 
cables are soldered or crimped securely. 
□ Compliant □ Incompliant 
Power cables and ground cables are routed and 
bundled separately from other cables. 
□ Compliant □ Incompliant 
Batteries are free from damage, cracks, and bulges.   
□ Compliant □ Incompliant 
Batteries are neat and do not leak electrolyte. 
□ Compliant □ Incompliant 
Wiring terminals of batteries are free from 
damage, break, and acid leakage. 
□ Compliant □ Incompliant 
Battery safety valves are intact, without leakages. 
□ Compliant □ Incompliant 
Battery cables are correctly connected, and the 
terminal voltages of battery strings are normal.   
□ Compliant □ Incompliant 
DIP switches on devices are correctly set.   
□ Compliant □ Incompliant 
 
Customer signature: 
Check date: