FusionModule2000 Smart Modular Data Center
Installation Guide
3 Smart Module Layout Requirements
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
34
Figure 3-10 Column in the aisle containment (A < 800 mm)
Cabinet places on the column side are left blank and sealed by sealing plates. Directions of the
concave sides of the sealing plates are shown in Figure 3-10.
Install cable trays over the cabinets on both sides of the blank cabinet places for routing
strong-current and weak-current cables.
Install an adjustable skylight over the aisle containment. The area to be covered by the adjustable
skylight is shown in Figure 3-10.