Typical power represents power under certain temperatures and normal operating conditions.
Table 89: MX960 Common Component Power Requirements
Typical Power RequirementMaximum Power RequirementComponent
50 W50 WBase system
400 W (normal speed)600 W (full speed)Normal-capacity cooling system
450 W (normal speed)640 W (full speed)High-capacity cooling system
Table 90: FRU Power Requirements
Maximum Power
RequirementPart NumberComponent
Switch Control Boards (SCB)
150 WSCB-MX (applies to MX240, MX480, and MX960)“SCB-MX” on page 168
160 W at 55° C
130 W at 40° C
120 W at 25° C
SCBE-MX (applies to MX240, MX480, and MX960)“SCBE-MX” on page 164
185 W at 55° C
160 W at 40° C
155 W at 25° C
SCBE2-MX (applies to MX240, MX480, and MX960)“SCBE2-MX” on page 157
275 W at 55° C
260 W at 40° C
245 W at 25 C°
SCBE3-MX (applies to MX240, MX480, and MX960)“SCBE3-MX” on page 149
Routing Engines