108: Recall Analog Line Configuration
This command recalls all kinds of information about an analog line's conversion, resolution,
calibration, alarm points, Hysteresis, alarm enabled/disabled status, etc. It intended to aid in
setting up the analog subsystem, not as a user command.
<108> l
Parameters:
- 108 is the default command name.
- L is the analog input line number (1..5)
Description of the voice response:
"analog ?" - which analog input on the I/O board we are referring to (1..5)
"0 volts is ?" - the lower calibration point
"5 volts is ?" - the upper calibration point
"calibrate ?" - how many units the calibration changes the reading
"low alarm ?" - the low alarm point
"high alarm ?" - the high alarm point
"h ?" - the amount of Hysteresis
"low alarm ?" - whether alarm is on or off
"high alarm ?" - whether alarm is on or off