14-11
Version 1.73 Copyright © 1997 Link Communications Inc. 1/18/97
RLC-ICM Internal Operation Test Points
The RLC-ICM ICOM IC900\901 module controller supports on-board function test points.
These test points are supported in the software release V1.14 and later. The test points are
located towards the center of the interface. Test points are located on connector J10 which is a
5 pin male header connector.
The following signals are present on J10.
Pin 1 - Transfer complete (Data received without errors)
Pin 2 - Configuration data received (Set-up data received without errors)
Pin 3 - Error detected in transfer (Errors were encountered on the RLC-ICM)
Pin 4 - 1 second pulse output (Indicates program is running)
Pin 5 - Ground reference
When any data is sent to the RLC-ICM one of the above pins will change state. The active
state is +5v or a (high). More than one state may be present at a time and the states will be
active for 10 seconds (Except the 1 second pulse output).
Controller interfacing:
The most common use for these signals is to read them with a voltmeter when
troubleshooting the RLC-ICM. They could also be connected to input lines on the controller to
provide remote feedback that commands were or were not transferred correctly, although this
should not be necessary once the RLC-ICM has been interfaced and tested.
When a frequency is selected on the interface, and the data was received without errors,
pin #1 will go from the low (0v) state to the high (5v) state. When connected to an input line
the controller can respond (Remote Base OK) for example. If an error is received during
transfer pin #3 will go from the low (0v) state to the high (5v) state. When connected to an
input line the controller can respond (Remote Base Error) for example. These lines simply tell
the user that the data was received.
These lines can not directly interface to LED's, relays or any current "hungry" device.
They are only designed for correct\error detection.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Link Communications RLC-CLUB and is the answer not in the manual?

Link Communications RLC-CLUB Specifications

General IconGeneral
BrandLink Communications
ModelRLC-CLUB
CategoryController
LanguageEnglish

Related product manuals