Operating the Drive 4-13
DC590+ Series DC Digital Drive
Step 9.2 Externally Supplied Field: (not available on Frame 1 units)
Refer to Chapter 3: “Installing the Drive” - Motor Field Options for conversion details.
Check the voltage applied (externally fused) to terminals FL1 and FL2.
Check the phasing of voltage applied to FL1 and FL2:
¾ FL1 must be connected directly or indirectly to the Red phase on main power terminal L1.
¾ FL2 must be connected directly or indirectly to the Yellow phase on main power terminal L2.
The FIELD ENABLE should be set to ENABLE.
With the FIELD ENABLE parameter in view, press the (DOWN) key. The display changes to FLD CTRL
MODE. Press the M key. Is this set to VOLTAGE CONTROL or CURRENT CONTROL?
¾ If set to VOLTAGE CONTROL, check the value of the FLD. VOLTS RATIO parameter. Set this to 65% to
obtain 300V fields from 460V supplies.
¾ If set to CURRENT CONTROL, check the field current calibration set-up, refer back to “Calibration”.
Check that 3-phase is applied to terminals L1, L2 and L3.
Step 10: Check the Keypad
Check that the HEALTH and RUN Keypad LEDs are now illuminated, also either the FWD or REV LED.
Step 11: Check the STANDSTILL LOGIC parameter
If the STANDSTILL LOGIC parameter in the STANDSTILL menu at level 2 is ENABLED, temporarily set it to
DISABLED.
Caution
During the following set-up instructions, be ready to STOP the drive should the motor try to overspeed.
If 5% speed (approximately) is exceeded and the motor continues to accelerate a reversed connection is implied, decrease the MAIN CURR.LIMIT
parameter to zero. Open the main contactor and disconnect all supplies. Reverse the motor connections.
MMI Menu Ma
p
1
SETUP PARAMETERS
2
FIELD CONTROL
FIELD ENABLE
MMI Menu Ma
p
1
SETUP PARAMETERS
2
FIELD CONTROL
3
FLD VOLTAGE VARS
FLD. VOLTS RATIO
MMI Menu Ma
p
1
SETUP PARAMETERS
2
CURRENT LOOP
MAIN CURR.LIMIT