LOCAL KEY ENABLE 511 FALSE / TRUE
Enables the LOCAL/REMOTE control key on the op-station. Set to TRUE to allow the operator to toggle between local and remote modes.
SETPOINT 512 0.00 to 100.00 %
SET UP menu - Actual value of local setpoint. This value is not persistent.
JOG SETPOINT 513 0.00 to 100.00 %
SET UP menu - Actual value of local jog setpoint. This value is not persistent.
RAMP ACCEL TIME 514 0.1 to 600.0 s
Acceleration time used while in Local mode.
RAMP DECEL TIME 515 0.1 to 600.0 s
Deceleration time used while in Local mode.
INITIAL DIR 516 REVERSE / FORWARD
START UP VALUES menu - Start-up mode of local direction on power-up. Set to TRUE for Forward.
INITIAL MODE 517 REMOTE / LOCAL
START UP VALUES menu - Start-up mode of Keypad LOCAL/REMOTE control key on power-up. Set to TRUE for Local mode.
INITIAL VIEW 518 LOCAL / PROGRAM
START UP VALUES menu - Start-up mode of Keypad PROG key on power-up. Set to TRUE for Program mode to see the local setpoint.