Technical Specifications E-27
DC590+ Series DC Digital Drive
Terminal Information (Frames 6 & H)
These terminals are located externally on the product.
Auxiliary Supply
Live 115-230V Frame 6
Auxiliary Supply
Live 110-240V Frame H
Auxiliary Supply
Neutral
These terminals are the mains input connections for control supply transformer and contactor relay supply L
N
Main contactor coil
V AC
This terminal is internally connected to the auxiliary supply neutral and provides a convenient connection point for
the contactor coil neutral connection
N
Main contactor coil
V AC
This terminal is the switched output from the contactor control relay and is derived from the auxiliary supply. The
output is internally fused at 3A hence contactor coils having a high pick-up current must be operated via a slave
relay.
Note: The contacts of the Contactor Control Relay are suppressed by a series connected resistor (680 Ohms) and
capacitor (22nF) to protect the relay contacts. Users should be aware that when the contactor Control Relay is
“De-energised”, a leakage current of approximately 2mA can be expected and this should be considered when
interfacing to these terminals. Typically, there could be the energisation of very sensitive relays.
C
Terminal Information – Option Boards
Terminal Description Terminal Function Signal Level Terminal Number
TERMINAL BLOCK G (SWITCHABLE TACHO CALIBRATION OPTION)
AC Tacho input AC G1
AC Tacho input AC G2
+ DC Tacho input +DC G3
- DC Tacho input -DC G4
Tacho Out Calibrated Tacho
Output
P3
(5701 MICROTACH RECEIVE OPTION - PLASTIC)
Signal Input Microtach fibre optic
input
There are no other connections to this option module. (The 5701 Microtach should be
powered by an external 24V DC at 60mA, 1.4W.)
F1