Cont. 4 
 
Product Warnings 
 
Caution 
Risk of electric shock 
 
Caution 
Refer to documentation 
 
Earth/Ground 
Protective Conductor Terminal 
Hazards 
DANGER! - Ignoring the following may result in injury 
1.  This equipment can endanger life by exposure to rotating 
machinery and high voltages.  
2.  The equipment must be permanently earthed due to the high 
earth leakage current, and the drive motor must be connected 
to an appropriate safety earth. 
3.  Ensure all incoming supplies are isolated before working on 
the equipment. Be aware that there may be more than one 
supply connection to the drive. 
4.  There may still be dangerous voltages present at power 
terminals (motor output, supply input phases, DC bus and the 
brake, where fitted) when the motor is at standstill or is 
stopped. 
5.  For measurements use only a meter to IEC 61010 (CAT III or higher). 
Always begin using the highest range.  
CAT I and CAT II meters must not be used on this product. 
6.  Allow at least 10 minutes for the drive's capacitors to discharge to safe 
voltage levels (<50V). Use the specified meter capable of measuring up 
to 1000V dc & ac rms to confirm that less than 50V is present between 
all power terminals and between power terminals and earth. 
7.  Unless otherwise stated, this product must NOT be dismantled. In the 
event of a fault the drive must be returned. Refer to "Routine 
Maintenance and Repair".