EasyManua.ls Logo

Parker 590+ series - Alarms

Parker 590+ series
545 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D-18 Programming
DC590+ Series DC Digital Drive
ALARMS
This block allows you to disable certain alarms and leave drive operation un-interrupted if the
related fault occurs.
Caution
Do NOT inhibit any alarms if this might result in danger to personnel
or equipment.
ALARMS
Parameter
Tag
Range
FIELD FAIL
19
ENABLED / INHIBITED
Inhibits the field fail alarm.
5703 RCV ERROR 111 ENABLED / INHIBITED
Inhibits 5703 serial communications receive error. Only active in Slave Mode.
STALL TRIP
28
ENABLED / INHIBITED
Inhibits the stall trip alarm from tripping out the contactor. This is useful in applications requiring extended operation at zero speed.
TRIP RESET 305 FALSE / TRUE
When FALSE: faults are latched permanently and the HEALTHY output remains inactive, even when toggling the Start/Run input (C3) off/on. Once
the drive is stopped the sequencing state remains in the SEQ HOLD state if any fault has been stored.
Changing from FALSE to TRUE clears any stored faults. Also, when TRUE: stored faults are cleared whenever a Run signal is given to terminal C3.
This feature can be used in applications where you want to reset the faults under your own control, rather than automatically with the Start/Run
command.
SPEED FBK ALARM
81
ENABLED / INHIBITED
Inhibits the speed feedback alarm.

Table of Contents

Related product manuals