D-12 Programming
DC590+ Series DC Digital Drive
Function Block Descriptions
NOTE Remember to select the correct mode, Setup or Configuration, whilst editing. Refer to “Modifying a Block
Diagram”, page D-1. To view the FUNCTION BLOCKS Menu, ADVANCED view level must be selected.
5703 IN
This function block contains the parameters for scaling the setpoint that are received via the P3 comms
port using the 5703 setpoint repeater protocol.
In the default configuration, the output of this block (SCALED INPUT) is added to analog inputs 1, 2
and 3 to form the setpoint.
5703 IN
Parameter
Tag
Range
SETPT. RATIO 132 -3.0000 to 3.0000
Input scaler.
SETPT. SIGN 133 NEGATIVE/ POSITIVE
Input sign.
SCALED INPUT 189
.xx %
The scaled value received by the 5703 unit. This value is updated upon reception of a new message. If the drive is in Slave mode and no new messages
have arrived, a 5703 RCV ERROR will occur.
Note: in software versions prior to 5.17, this input is not updated when in Master mode.
RAW INPUT 187
.xx %
The unscaled value received via the P3 port.