EasyManua.ls Logo

Parker 590+ series - Step 15: Fine Adjustments for Speed Feedback; Step 16: Adjustment for Field Weakening

Parker 590+ series
545 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-16 Operating the Drive
DC590+ Series DC Digital Drive
Step 15: Fine adjustments for Speed Feedback
Gradually increase the Speed Setpoints so that the value of the SPEED SETPOINT (DIAGNOSTIC menu) is at maximum.
Check the shaft speed is correct.
If fine adjustment is required adjust the calibration as appropriate to the speed feedback selection:
Armature Voltage feedback has a +2/-10% trim, greater changes outside this range require re-setting of the calibration
switches.
Analog Tachogenerator has a +2/-10% trim, greater changes outside this range require re-setting of the calibration
switches.
The MICROTACH/Encoder should give an absolute rotational speed for which adjustment is unnecessary however the motor speed may not be the
relevant factor thus speed of rotation can be altered by simply adjusting the calibration.
Step 16: Adjustment for Field Weakening
If the drive is to be run with a top speed greater than the base speed then `field weakening’ is used to achieve that top speed.
(Refer to Chapter 5: “Control Loops” - Field Control for a more detailed explanation).
NOTE The drive must be operating in Field Current Control. Select CURRENT CONTROL on the FLD CTRL MODE
parameter. Also, field weakening cannot be used if you have Armature Voltage feedback selected.
IR COMPENSATION (CALIBRATION function block) is also used in field weakening applications to improve dynamic response and speed holding
stability.
To set up IR COMPENSATION:
Set FIELD ENABLE to DISABLED (FIELD CONTROL function block). Start the drive with a 5% speed demand and ensure the ACTUAL
POS I LIMIT is 100% (diagnostic). This should stall the drive at zero speed and cause it to pass 100% current. Monitor the BACK EMF
diagnostic and note the value (typically anything up to 17% is normal). Stop the drive and enter this value into IR COMPENSATION and
repeat the test to ensure that BACK EMF then reads zero.
Run the drive up to base speed and check the motor volts are correct.
In the FLD WEAK VARS menu, verify that field weakening is selected (FIELD WEAK ENABLE) and that the MIN FLD
CURRENT parameter is set appropriately. Adjust the maximum BEMF volts to the required scaled level by setting the MAX
VOLTS parameter.
Increase the speed above the base speed, checking that the armature volts remain constant whilst the field current reduces.
Gradually increase to maximum speed. Monitor the armature volts at maximum speed and trim the speed using the
appropriate control as detailed in Step 15. PROCEED WITH CARE - MAKE SMALL ADJUSTMENTS.
Trim the MIN FLD CURRENT parameter to the appropriate setting (5% lower than the field current at full speed).
MMI Menu Ma
p
1
SETUP PARAMETERS
2
CALIBRATION
ARMATURE V CAL.
ANALOG TACH CAL.
ENCODER RPM
MMI Menu Ma
p
1
CONFIGURE DRIVE
FLD CTRL MODE
MMI Menu Ma
p
1
SETUP PARAMETERS
2
FIELD CONTROL
3
FLD CURRENT VARS
4
FLD WEAK VARS
FLD. WEAK ENABLE
MIN FLD CURRENT
MAX VOLTS

Table of Contents

Related product manuals