Installing the Drive 3-19
DC590+ Series DC Digital Drive
Power Connections continued
Protective Earth Connections
PE
Connect the
drive's PE
terminal to an
independent
earth/ground
star point.
Connect this
earth/ground
star point to
Protective
Earth.
IMPORTANT
The drive and filter (if fitted) must be permanently earthed. Each conductor used for
permanent earthing must individually meet the requirements for a protective earth
conductor.
For installations to EN 60204 in Europe:
For permanent earthing, the drive requires either two individual incoming protective earth conductors (<10mm²
cross-section), or one conductor (10mm² cross-section) connected to an independent protective earth/ground
point near the drive.
Run the motor protective earth/ground connection in parallel with the motor supply conductors, ideally in the
same conduit/screen/armour, and connect to an independent protective earth/ground point near the drive.
Refer to Appendix B: “Certification” - EMC General Installation Considerations.
Caution
On the Frame 5, both the Master and Slave drives must be individually earthed.
Motor Armature
A+
A-
Connect the
motor
armature to
terminals A+
and A-.
Connect the cable screen to the motor's PE terminal and the earth/ground star point.
Connect the motor's PE terminal to the earth/ground star point.
For cable information refer to Appendix B: "Certification" - Recommended Wire Sizes.
NOTE If the drive is to operate in regenerating mode for long periods, it is
advisable to fit a dc fuse or high speed circuit breaker in the armature
circuit. If in doubt consult Parker SSD Drives.
+
PE
M
A+ A
-
PE
star
point