Trips and Fault Finding  7-11 
DC590+ Series DC Digital Drive    
Frame 6 
Eight diagnostic LEDs indicate further trip information, and general status of the unit. The LEDs go out to indicate a problem (note that LED1 may 
also flash as the SMPS attempts to power-up repeatedly, indicating a fault).  
Trips 
 
Power Board 
  switched mode power supply on  SMPS OK
|
LED1 
trigger board connection status  TRIGGER BOARD PRESENT
|
LED9 
ACCTS FAILED 
ac current transformer connection status  ACCTS PRESENT
|
LED10 
3 PHASE FAILED  thyristor fuses status  THYRISTOR FUSES
|
LED11 
field heatsink temperature normal  FIELD THERMOSTAT
|
LED12 
L1 Phase Assembly heatsink temperature 
normal 
L1 STACK THERMOSTAT | LED13 
L2 Phase Assembly heatsink temperature 
normal 
L2 STACK THERMOSTAT | LED14 
L3 Phase Assembly heatsink temperature 
normal 
L3 STACK THERMOSTAT | LED15 
HEATSINK TRIP 
Fans stalled  L* FAN
|
Fan LEDS 
 
*  In the event of a trip due to a stalled fan, an unlit fan LED will indicate the failed fan. With the drive stopped, operate the fan fail override switch 
and restart the drive. Diagnose the failed fan from the fan LEDs status.