3-6 Installing the Drive
DC590+ Series DC Digital Drive
Ventilation and Cooling Requirements
NOTE When fitting a drive into a sealed enclosure additional cooling MUST be provided, otherwise the internal air will
overheat causing the drive to trip on "overtemperature".
Refer to Appendix E: “Technical Specifications” - Cooling Fans.
The Drive gives off heat during normal operation and must therefore be mounted to allow the free flow of air through the air entries and exits.
Maintain the minimum air clearances given on the drawings to ensure that heat generated by other adjacent equipment is not transmitted to the Drive.
Be aware that other equipment may have its own clearance requirements. When mounting two or more DC590+’s together, these clearances are
cumulative.
Ensure that the mounting surface is normally cool.
Installing the Fan (Frame H)
Refer to Appendix E: “Technical Specifications” - Cooling Fans.
The fan unit supplied should be installed on the cubicle, with or without ducting (refer to the Installation Drawing). The drive is force-cooled using the
fan units supplied with the drive. As a general rule allow at least 150mm (6 inches) of clear space above and below the drive for free air flow. We
suggest the cubicle has an air inlet at the base of the cubicle equivalent to 0.37m
2
(4ft²), variable depending upon the filter type used, to allow the
maximum throughput of air.
The fan assembly provided is permanently wired as shown below.
Figure 3- 2 Frame H Fan Wiring Diagram
115V ac
1
2
3
4
PE/GRD
L
N
115V ac + 10%
50/60Hz
230V ac
1
2
3
4
PE/GRD
L
N
230V ac + 10%
50/60Hz
L
N
L
N
L
N
L
N
4.5A
2.25A
PE/GRD
FN4
FN3
FN2
FN1