Cont. 5 
 
WARNING! - Ignoring the following may result in injury or damage to equipment 
SAFETY 
Where there is conflict between EMC and Safety requirements, personnel safety shall always take precedence. 
•  Never perform high voltage resistance checks on the wiring without 
first disconnecting the drive from the circuit being tested. 
•  Whilst ensuring ventilation is sufficient, provide guarding and /or 
additional safety systems to prevent injury or damage to equipment. 
•  When replacing a drive in an application and before returning to use, 
it is essential that all user defined parameters for the product’s 
operation are correctly installed. 
•  All control and signal terminals are SELV, i.e. protected by double 
insulation. Ensure all external wiring is rated for the highest system 
voltage. 
•  Thermal sensors contained within the motor must have at least 
basic insulation. 
•  All exposed metalwork in the Drive is protected by basic insulation 
and bonded to a safety earth. 
•  RCDs are not recommended for use with this product but, where 
their use is mandatory, only Type B RCDs should be used. 
EMC 
•  In a domestic environment this product may cause radio interference 
in which case supplementary mitigation measures may be required. 
•  This equipment contains electrostatic discharge (ESD) sensitive 
parts.  Observe static control precautions when handling, installing 
and servicing this product. 
•  This is a product of the restricted sales distribution class according 
to IEC 61800-3. 
•   It is designated as “professional equipment” as defined in 
EN61000-3-2. Permission of the supply authority shall be obtained 
before connection to the low voltage supply.