Trips and Fault Finding 7-9
DC590+ Series DC Digital Drive
When more than one trip is to be represented at the same time then the trip codes are simply added together to form the value displayed. Within each
digit, values between 10 and 15 are displayed as letters A to F
For example, if the HEALTH WORD parameter is 01A8 then this represents a “1” in digit 3, an “8” and a “2” in
digit 2, (8+2 = 10, displayed as A) and an 8 in digit 1. This in turn represents the active trips FIELD FAILED,
ENCODER FAILED, OVER VOLTS (VA) and HEATSINK TRIP (an unlikely situation).
Power Board LED Trip Information (Frame 4, 5, 6 & H)
The HEATSINK TRIP, 3 PHASE FAILED and ACCTS FAILED trips are associated with the following LED indications:
Frame 4
Check the LEDs on the power board for more HEATSINK TRIP information.
The LEDs light to indicate a problem.
FLD HS OT
ARM HS OT
PHASE LOSS
field heatsink overtemperature
armature heatsink overtemperature
phase loss
HEATSINK TRIP
3 PHASE FAILED
Trips
Decimal number Display
10 A
11 B
12 C
13 D
14 E
15 F