EasyManua.ls Logo

Parker 590+ series - Electrical Ratings - Power Circuit; Cont

Parker 590+ series
545 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E-6 Technical Specifications
DC590+ Series DC Digital Drive
Electrical Ratings - Power Circuit
Refer to Chapter 3: “Earth Fault Monitoring Systems” for circuit breaker details.
Motor HP ratings as NEC Table 430-147: “Full Load Current in Amperes, DC Motors”’
Output Current @
150% and 200% *
(A)
Output Current @ 100%
Continuous *
(A)
Power @ 500V dc
(kW)
Motor HP @ 500V
dc
(HP)
Field Current
(A)
Total Losses @ Full
Load
(W)
Symmetrical Fault
Current rms
(kA)
Frame 1
15 15 7 7.5 4 57 5
35 35 15 20 4 117 5
Frame 2
40 40 18 25 10 132 10
70 70 30 40 10 234 10
110 110 50 60 10 354 10
165 165 75 100 10 519 10
Frame 3
180 180 80
50
10 570 10
270 270 120 150 10 840 10
Frame 4
380 420 150
200
30 1230 18
500 550 225
300
30 1590 18
725 800 327
400
30 2265 30
830 910 335
500
30 2580 30
Frame 5
1580 1740 650
900
30 4890 85
Frame 6
1250 1350 600 800 60 4600 100
1600 1750 750 1000 60 5000 100
1950 # 2150 900 1200 60 6000 100

Table of Contents