EasyManua.ls Logo

Parker 590+ series - Page 281

Parker 590+ series
545 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Certification B-9
DC590+ Series DC Digital Drive
Recommended Wire Sizes (Frame 6)
Local wiring regulations always take precedence.
Input Output
Description Drive
Size
(A)
Input Current
(A)
Number of
Conductors
North American
Wire Size
(Kcmil)
Output Current
(A)
Number of
Conductors
North American
Wire Size
(Kcmil)
1250 1125 4 500 1250 4 500
1650 1485 6 400 1650 6 500
Main
Power
1950 1755 6 500 1950 6 600
Field 60 60 1 AWG 8 60 1 AWG 8
Recommended Wire Sizes (Frame H)
Local wiring regulations always take precedence.
Input Output
Description Drive
Size
(A)
Input Current
(A)
Number of
Conductors
North American
Wire Size
(Kcmil)
Output Current
(A)
Number of
Conductors
North American
Wire Size
(Kcmil)
1200 1100 4 500 1200 4 500
1700 1550 6 400 1700 6 500
2200 2000 6 600 2200 6 700
Main
Power
2700 2450 6 900 2700 8 700
Field 60 60 1 AWG 8 60 1 AWG 8
Field Grounding Terminals
The field grounding terminals are identified with the International Grounding Symbol
(IEC Publication 417, Symbol 5019).
Operating Ambient Temperature
0°C to 40°C (32°F to 104°F), derate up to a maximum of 50°C. Derate linearly at 1% per degree centigrade for temperature exceeding the maximum
rating ambient for the drive.
External Power Semiconductor Protection Fuses
For details on these input fuses, refer to Appendix E: "Technical Specifications".

Table of Contents