D-20 Programming
DC590+ Series DC Digital Drive
ALARMS
Parameter
Tag
Range
STALL TRIP 112 FALSE / TRUE
Armature current is above STALL THRESHOLD and AT ZERO SPEED but not AT ZERO SETPOINT.
LAST ALARM
528
0x0000 to 0xFFFF
The hexadecimal value of the last (or only) alarm. Refer to Chapter 7: “Trips and Fault Finding” - Alarm Messages.
0x0000 : NO ACTIVE ALARMS
0x0001 : OVER SPEED
0x0002 : MISSING PULSE
0x0004 : FIELD OVER I
0x0008 : HEATSINK TRIP
0x0010 : THERMISTOR
0x0020 : OVER VOLTS (VA)
0x0040 : SPD FEEDBACK
0x0080 : ENCODER FAILED
0x0100 : FIELD FAILED
0x0200 : 3 PHASE FAILED
0x0400 : PHASE LOCK
0x0800 : 5703 RCV ERROR
0x1000 : STALL TRIP
0x2000 : OVER I TRIP
0x8000 : ACCTS FAILED
0xF001 : AUTOTUNE ERROR
0xF002 : AUTOTUNE ABORTED
0xF003 : SEQ PRE READY
0xF004 : CONTACTOR DELAY
0xF005 : EXTERNAL TRIP
0xF006 : REMOTE TRIP
0xF007 : ENABLE LOW
0xF009 : SEQUENCING
0xF010 : COMMS TIMEOUT
0xF200 : CONFIG ENABLED
0xF300 : CALIBRATION
0xF400 : NO OP-STATION
0xFF03 : AUX SUPPLY
0xFF05 : PCB VERSION
0xFF06 : PRODUCT CODE