Programming D-27
DC590+ Series DC Digital Drive
AUTOTUNE ABORTED User abort of the process.
FIRING ANGLE Firing angle has reached 60deg. before zero voltage crossing, in an attempt to derive a 60deg. wide pulse likely
absent armature or severely resistive load.
PEAK/AVER.RATIO Badly shaped current pulse, where the pk/average current ratio is more than 30% away from expected 1.5.
UNBALANCED BRID. Pulse size imbalance greater than that from a motor BEMF equivalent to 5deg. from zero voltage crossing likely
poorly balanced supply phases or motor shaft turning.
NULL AVERAGE CUR No current pulses detected.
THYRISTOR OFF Missing pulse detectedlikely missing firing pulses from one or more thyristors.