JOG/SLACK 496 OFF / ON
Main jog input which is connected to DIGITAL INPUT C4 by default. The Jog input is ANDed with Auxiliary Jog input, Tag 227, to generate Drive
Jog.
ENABLE 497 OFF / ON
Enable input which is connected to DIGITAL INPUT C5 by default. The Enable input is ANDed with Auxiliary Enable input, Tag 168, to generate
Drive Enable.
REM.SEQ.ENABLE 535 FALSE / TRUE
(Refer to Chapter 4: "External Control of the Drive"). When enabled, the drive will accept Sequencing commands exclusively from the REM.
SEQUENCE parameter, Tag 536.
FALSE - disables REM. SEQUENCE
TRUE - enables REM. SEQUENCE
REM.SEQUENCE 536 0x0000 to 0xFFFF
A control word that allows the device to be operated remotely over a field bus.
REM. SEQ. ENABLE must be TRUE to enable this function. (Refer to Chapter 4: "External Control of the Drive")
COMMS TIMEOUT 1204 0.0 to 60.0 s
A watchdog timeout that may be used when the drive is in remote sequencing mode. The watchdog feature is enabled by selecting a non-zero time in
this parameter. The watchdog is reset every time the REM.SEQUENCE word, (Tag 536), is written.
SEQ STATUS 537 0x0000 to 0xFFFF
An data word that reports the status of the important system flags that can be read over a field bus. (Refer to Chapter 4: "External Control of the
Drive")
DRIVE START 82 OFF / ON
Logical OR of the START and JOG inputs.
CONTACTOR CLOSED 83 FALSE / TRUE
When ON, the main contactor coil is energised. Refer to Terminal Information for D5 & D6 in Appendix E: "Technical Specifications" - Terminal
Information.
DRIVE ENABLE 84 FALSE / TRUE
Drive speed and current loop are enabled/quenched.
DRIVE RUNNING 376 FALSE / TRUE
When TRUE, the stack is switched on and enabled.