Programming D-115
DC590+ Series DC Digital Drive
SETPOINT SUM
Parameter
Tag
Range
LIMIT
375
0.00 to 200.00 %
The Setpoint Sum programmable limit is symmetrical and has the range 0.00% to 200.00%. The limit is applied both to the intermediate results of
the RATIO calculation and the total output.
-1
LIMIT
INPUT 2
INPUT 1
INPUT 0
SPT SUM OUTPUT 86
.xx %
The sum of input 0, 1 and 2 after the limit clamp.
STPT SUM 1 OUT 1 702
.xx %
An additional output provided to gain access to Input 1 channel sub-calculations. The result of (INPUT 1 x RATIO 1) / DIVIDER 1 clamped to
within LIMIT.
STPT SUM 1 OUT 0 703
.xx %
An additional output provided to gain access to Input 0 channel sub-calculations. The result of (INPUT 0 x RATIO 0) / DIVIDER 0 clamped to
within LIMIT.