E-10 Technical Specifications
DC590+ Series DC Digital Drive
AC Line Choke (Frames 1-5)
To correctly isolate the DC590+ drive from the ac power system, and to protect other equipment from transients on the power system, always use the
recommended external ac line choke (or alternatively a transformer may achieve the necessary isolation).
Note that the Frame 5 requires two ac line chokes (one in front of each of the paralleled drives). This provides isolating impedance between the
drive and its ac power source. It also provides the necessary impedance between the paralleled drives, forcing them to share the total motor current
evenly. The Frame 5 drive must still use two ac line chokes when a transformer is used for isolation, however, the chokes can be of a much lower
inductance, typically 3-5 µH.
Drives below 100A Armature Current rating cannot achieve conformance with EN61800-3 Table 17 using only a 50H line choke. Capacitors must
be fitted between phase and earth to achieve conformance. Refer to Chapter 3: "Installing the Drive" - Filtering.
Armature Current Rating (A) AC Rating (A) Inductance (μH) Parker SSD Drives Part No.
500Vac 600Vac 500Vac 600Vac
AC Line Chokes @ 1% line impedance for conformance with EN618003 (2004) Table 14 Category C2 when used with specified filters.
Frame 4
380 342 - 30 μH - CO466709U038
500 450 - 25 μH - CO466709U050
725 653 - 20 μH - CO466709U073
830 747 - 15 μH - CO466709U083
Frame 5 (2 chokes required)
0831-1200 747 - 20 μH - CO466709U073
0831-1200
(use with transformer only)
747 - 5 μH - CO466709U120
1201-1580 747 - 15 μH - CO466709U083
1201-1580
(use with transformer only)
747 - 5 μH - CO466709U160