Fieldbuses A-43
AC30 series Variable Speed Inverter
9. Configure the process data for the slave.
By clicking on the slave, the input and output process data may be
configured. This must match the configuration set up in the AC30.
The appropriate input and output modules may be dragged from the
catalogue and dropped into the appropriate slot. All output modules
must come before the input modules.
The default modules will be seen already plugged. These may be
changed as necessary.
10. Set the required update time.
Double click on the PROFINET IO System and click on the
Update Time tab. The update time of the AC30 may be changed.
11. Save, compile and download.
Make sure the PC/PLC interface is connected. Select Station from the menu and Save and Compile then select PLC and Download…