A-50 Fieldbuses
AC30 series Variable Speed Inverter
Example Acyclic Access of Parameters
A CoDeSys (V3.5 SP11) soft PLC running on a PC is used. In this example, two parameters are accessed:
• Reading from parameter 0005 Digin Value of data type WORD
• Writing to parameter 0305 Current Limit of data type REAL
Example structured text code to access these parameters acyclically is shown below.