Parameter Reference C-3
AC30 series Variable Speed Drive
The correct installation requires the following components:
- LCL filter
o 3% and 5% chokes (as part of an LCL filter, custom designed )
o Capacitor panel (as part of an LCL filter, custom designed)
- Pre-charge resistor with external pre charge control
- Thee phase contactors
- EMC filter (optional)
- AC Line fuses
- DC Link fuses
- Line sync card (LA471892U001)
- Encoder option card (7004-04-00)
Drive Set-up
Typically the system will contain an AC30P/AC30D regen drive providing 4-Q power supply, and one or more drives on the common DC bus.
ALL drives in the system MUST have their internal EMC “Y” caps to earth disconnected.
A 4-Q regen drive is set into AFE control mode by setting the Control Mode “Motor Type or AFE parameter to AFE as shown in picture below.
This setting must be accompanied by selection of an appropriate AFE macro from the default application:
If the “Motor Type or AFE and “Selected Application” do not match, it would not be possible to operate the drive correctly.Both these settings are
necessary for proper configuration of the drive to work as an active front end.
When drive is in AFE mode, its current rating is limited to 85% of the equivalent set up current rating when in one of the motor modes.
The standard set of AFE parameters required to finalise the drive AFE configuration are located within Setup/Regen Control menu. Based on the
“AFE Current Control” bit, AFE would operate in voltage control mode (left), or current control mode (right):

Table of Contents

Other manuals for Parker AC30 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC30 series and is the answer not in the manual?

Parker AC30 series Specifications

General IconGeneral
Control ModesClosed-loop vector
FeedbackEncoder
Operating Temperature0 to 40°C (32 to 104°F) standard, -20 to 50°C (-4 to 122°F) with derating
ProtectionOvercurrent, Overvoltage, Undervoltage
CommunicationRS485

Related product manuals