Parameter Reference C-15 
AC30 series Variable Speed Drive 
Auto Restart 
Setup:: Motor Control::Auto Restart 
Parameters::Motor Control::Auto Restart 
The Auto Restart feature provides the facility to automatically reset a choice of trip events and restart the drive with a programmed number of 
attempts. The number of attempted restarts is monitored. A manual or remote trip reset is required if the drive is not successfully restarted within the 
maximum number of restarts. The purpose of this feature is to allow automatic recovery from trip conditions. This is especially useful on remote or 
unmonitored sites. 
 
AR Enable 
 
1469 
 
Setup::Motor Control::Auto Restart 
Parameters::Motor Control::Auto Restart 
FALSE 
 
ALWAYS 
 
Enables the auto restart function. 
AR Mode 
 
1470 
 
Same as PNO 1469 
 
1 
 
0:TRIP RESET 
1:AUTO RESTART 
2:AUTO START 
ALWAYS 
 
Defines the action that the AR function will take following a trip. 
0.  TRIP RESET    Trips will be reset when the trip sources are inactive. The drive will not be restarted. 
1.  AUTO RESTART  If it was running the drive will be restarted when the trip sources are inactive and run is active. 
2.  AUTO START    The drive will be started when the trip sources are inactive if the run signal is high 
Refer to the Functional Description below for more details. 
AR Max Restarts 
1471 
 
Same as PNO 1469 
 
10 
 
1 to 20 
 
ALWAYS 
 
Defines the maximum number of restart attempts permitted before the AR function disables itself.