C-18 Parameter Reference
AC30 series Variable Speed Drive
Indicates that the AR feature will reset the trip source once all trips have become inactive, (following a delay time if the AR feature has
been configured to also restart the motor).
AR Restart Pending
1508
Parameters::Motor Control::Auto Restart
NEVER
Indicates that the AR feature will reset the trip source and attempt to restart the motor once all trips have become inactive and the
relevant delay timer has expired.
AR Restarts Remaining
1509
Parameters::Motor Control::Auto Restart
0 to 20
NEVER
Indicates the number of restart attempts remaining before the AR feature disables itself.
This count is reset to 1471 AR Max Restarts after a successful manual or remote trip reset. The count is also reset after a period of
trip free operation. This period is the longer of 5 minutes, or 5 * AR Repeat Delay B.
AR Time Remaining
1510
Parameters::Motor Control::Auto Restart
0.000 to 3600.000
s
NEVER
Indicates the time remaining before a restart attempt will be made. This value starts to count down once all trip sources are inactive.
Functional Description
The AR feature can be configured to operate in one of three modes via the parameter 1470 AR Mode.
In all modes the AR feature becomes active when the drive trips on one of the trips selected by parameter 1472 AR Trip Mask. If the drive trips due
to a trip not selected in 1472 AR Trip Mask the AR feature will remain in the idle state.
Setting parameter 1469 AR Enable to FALSE will disable the AR feature regardless of its current state.
1470 AR Mode 0: Trip Reset
In Trip Reset mode, once the AR feature becomes active it monitors all possible trip sources. Once all trip sources are inactive the AR feature will
attempt to reset the trip event, moving the Sequencing State from the FAULTED state, (see Appendix B: Sequencing Logic). The AR feature resets
the trip as soon as possible, it does not wait for either 1505 Initial Delay or 1506 AR Repeat Delay.
In this mode the AR feature will not attempt to restart the motor.