C-56 Parameter Reference
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
IO Option FE State
0996
Parameters::Device Manager::Device
State
Same as PNO 989
NEVER
System Board FE State
1742
Parameters::Device Manager::Device
State
Same as PNO 989
NEVER
The parameters above indicate the state of individual components, (or Functional Elements), within the drive. They may help with fault
finding if the drive ever fails to enter the normal Operational state.
Config Fault Area
0997
Parameters::Device Manager::Device
State
0:NONE
1:POWER STACK
2:OPTION IO
3:OPTION COMMS
4:APPLICATION
5:MOTOR CONTROL
6:KEYPAD
7:BASE COMMS
8:BASE IO
9:FEEDBACK MISSING
10:SYSTEM BOARD
NEVER
Indicates which component within the drive is preventing the drive from entering the normal Operational state.
RTA Code
0998
Monitor::Trips
Parameters
::Device Manager::Device
State
NEVER
Run Time Alert fault code, indicates a fault in the hardware or configuration, typicaly detected during power on initialization. Refer to
chapter 7, Trips and Fault Finding.
RTA Data
0999
Same as PNO 998
NEVER
Data associated with a Run Time Alert.

Table of Contents

Other manuals for Parker AC30 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC30 series and is the answer not in the manual?

Parker AC30 series Specifications

General IconGeneral
Control ModesClosed-loop vector
FeedbackEncoder
Operating Temperature0 to 40°C (32 to 104°F) standard, -20 to 50°C (-4 to 122°F) with derating
ProtectionOvercurrent, Overvoltage, Undervoltage
CommunicationRS485

Related product manuals